Firestopping inspection checklist

Firestopping is inspected penetration by penetration, and every one of them has to match a listed system. A photograph of the applied material next to the identifying label is what turns a wall full of red caulk into an auditable record.

Items
13
Photos required
27

Who runs it

Firestop installer; the GC and the special inspector verify against the listed systems.

When in the schedule

As each rated assembly is penetrated and before the ceiling closes. Re-walk after every late trade cuts a new hole.

The checklist

Every item, and the photo that proves it

The photo count on each row is what RTI would require before the item can be submitted. Copy the list as-is, or load it into RTI and let the gate enforce it.

01

Identify the assembly

  • Rated walls and floors identified on the drawings and in the field

    Walk with the life-safety plan; know the rating before choosing a system.

    2 photos
  • Rated walls labelled above the ceiling at required intervals

    Permanent, legible marking so a future trade knows what it is cutting.

    2 photos
  • Assembly built as rated before firestopping begins

    Board to deck, correct layers, no unrated gaps at the top track.

    2 photos
02

Penetrations

  • Each penetration matched to a listed system

    Penetrant type and size, assembly type and rating all match the system number cited.

    3 photos
  • Annular space within the listed range

    Measure and photograph the gap before it is filled.

    2 photos
  • Correct product, depth and packing material installed

    Backing material where the system requires it; depth as listed, not as convenient.

    3 photos
  • Sleeves and devices installed per the system

    Collars, wraps and cast-in devices oriented and fastened as detailed.

    2 photos
03

Joints and voids

  • Head-of-wall joints firestopped to the listed detail

    Correct movement capability; the detail differs between deflection and static joints.

    2 photos
  • Perimeter and floor edge joints sealed

    Continuous at the slab edge with the specified backing.

    2 photos
  • Blank openings and abandoned penetrations closed

    Anything cut and not used gets closed to the rating, not covered over.

    2 photos
04

Documentation

  • Identification label applied adjacent to each firestop

    System number, installer, date and product legible in the photo.

    2 photos
  • Location log maintained against the plan

    Each penetration traceable to a drawing location and a photo.

    1 photo
  • Re-walk after late penetrations

    A second, dated pass once low-voltage and specialty trades finish.

    2 photos

What usually sends this back

The failures are almost always the evidence, not the work

  • One product used everywhere regardless of the penetrant and the assembly it passes through.
  • Annular space larger than the listed system allows, sealed anyway.
  • Late penetrations cut after the firestop walk and never re-inspected.

Run it with the Photo Gate

A checklist nobody can submit half-finished

Load this list into RTI, stick a QR tag on the area it covers, and the submit button stays locked until every mandatory item is answered and the 27 required photos exist. Approved walks roll into a branded turnover package with a tamper-evident record behind every line.

Submission state

Mandatory items answered13 of 13
Photos attached24 of 27
Submit locked — 3 photos missing

The gate is enforced on the server, so it holds even if the phone is offline when the walk happens.