Free checklist
InsulationInsulation rough-in inspection checklist
Insulation rough-in is the last time the work is fully visible. Once the cover inspection passes and the walls, ceilings and slabs close, every defect left behind becomes a demolition bill. This checklist walks the rough-in in the order the work goes in, with the photo each item needs before it gets buried. Work is commonly verified against the applicable energy code. Confirm the edition your authority having jurisdiction has adopted.
The checklist
Every item, and the photo evidence it needs
The photo count on each row is what RTI would require before the item can be submitted. Work the list here and watch the gate hold, or load it into RTI and let it enforce the real thing.
Materials on site
Delivered product type and facing match the spec
Bundle or bag labels show the specified product (batt, board or blown fill) and facing (kraft, foil or unfaced) for each assembly before any of it goes in.
Stock stored covered and off the slab
Bundles and bags kept dry, off the slab and out of traffic; any that got rained on or were flattened under other material tagged and kept out of the walls.
Cavity fill
Batts fill the full depth and width of each cavity
Insulation in contact with all six sides of the bay, no compression, no voids at corners or edges.
Insulation split and fitted around obstructions
Batts cut around pipes, wiring and boxes rather than stuffed behind them, no crushed sections.
Installed R-value matches the spec for the assembly
Product label or bag tag photographed in place, matching the R-value called out for that wall or ceiling.
Batts held in place the way the product instructions show
Faced flanges inset or face-stapled flat along the stud with no gaps or fishmouths; unfaced batts friction-fit so they stay put without sagging.
Narrow bays beside openings and corners filled
Cut pieces in the short bays next to windows, doors and wall intersections, and in headers and jack spaces the framing left open.
Top-of-wall and band bays filled, not skipped
Bays at the top plate and at any rim or band joist filled tight with cut batt or board, not a loose batt draped across or left for later.
Air sealing coordination
Gaps at top and bottom plates sealed
Foam or sealant at plate lines, penetrations and rim areas per the air-sealing scope.
Chases and soffits blocked and insulated
Dropped soffits, tub decks and chases capped with a rigid barrier and insulated to the same level as the surrounding assembly.
Attic and ceiling work
Blown or batt depth consistent across the attic
Depth markers visible and depth checked at multiple points, baffles holding insulation clear of the eave vents.
Attic access and mechanical platforms insulated to spec
Access cover insulated and weatherstripped, walk platforms not creating uninsulated voids.
Ceiling fixtures and fans checked for IC rating before cover
Each light, fan housing and flue through the insulated ceiling located; IC rating read off the label, non-IC items and flues dammed back to the listed clearance.
What usually sends this back
The failures are almost always the evidence, not the work
- Batts stuffed around pipes and wiring instead of split and fitted, leaving voids nobody can see after cover.
- R-value assumed from the order ticket rather than read off the batts actually installed.
- Top-of-wall and rim band gaps skipped because the ladder work is slow.
Verified against
Common questions
6 answers
- What does this insulation rough-in checklist cover?
- 13 items across 4 sections, covering materials on site, cavity fill, air sealing coordination, attic and ceiling work. Each item spells out what the person walking the job is actually looking for, not just a box to tick.
- Who should run this inspection?
- The insulation foreman walking their own bays, or the GC's superintendent spot-checking a floor before drywall is released.
- When in the schedule should this walk happen?
- As each area is filled, before drywall, sheathing or ceiling cover is scheduled on that area.
- Why does every item ask for a photo?
- All 13 items call for photo evidence, 18 photos in all. A checklist answer without the photo is a claim; the photo is what makes the record worth something in a dispute and lets a reviewer approve work without re-walking the job.
- What most often fails an insulation rough-in inspection?
- Batts stuffed around pipes and wiring instead of split and fitted, leaving voids nobody can see after cover. R-value assumed from the order ticket rather than read off the batts actually installed. Top-of-wall and rim band gaps skipped because the ladder work is slow.
- Can I use this checklist in RTI?
- Yes. Start a free RTI workspace, build this list as a checklist, and the Photo Gate holds the submit button until every mandatory item is answered and its photos are attached. Approved inspections roll into a branded turnover package with a tamper evident audit trail.
Related checklists
Run it with the Photo Gate
A checklist nobody can submit half-finished
Load this list into RTI, stick a QR tag on the area it covers, and the submit button stays locked until every mandatory item is answered and the 18 required photos exist. Approved walks roll into a branded turnover package with a tamper evident record behind every line.
See all 508 checklists · 6741 items and 5984 photo requirements in total.