Checklists by trade
Fire protection inspection checklists
Fire protection inspection checklists for the rough-in, pre-cover, final and preventive maintenance walks: 4 free lists, 54 items and 56 photo requirements, each item naming what to look for and the photo evidence it needs. Work is commonly verified against NFPA 13 and NFPA 25; the edition in force is the AHJ's call on each project.
The fire protection walks, in build order
Where each walk sits in the schedule
01rough-in
Fire protection rough-in inspection checklist
After branch lines and mains are hung and before ceiling grid or drywall closes in, and before the AHJ rough-in inspection is called.
Run by: The sprinkler foreman walking their own rough-in with the GC's superintendent.
02pre-cover
Fire protection pre-cover inspection checklist
After the branch lines and mains are complete and hydrostatically tested, before ceiling tile or hard lid closes the space above.
Run by: The sprinkler foreman with the GC's superintendent, releasing the area once the test is documented.
03final
Fire protection final inspection checklist
After escutcheons and covers are installed and the system is charged, before final acceptance testing and turnover.
Run by: The sprinkler foreman at trim-out, then the fire marshal or AHJ at final acceptance testing.
04preventive maintenance
Fire protection preventive maintenance checklist
Monthly and quarterly rounds per the maintenance schedule, with an annual full system test.
Run by: The fire protection contractor or in-house fire life-safety tech on a scheduled inspection round.
What most often sends fire protection work back
- Head locations laid out to the sprinkler drawing but never checked against the actual reflected ceiling plan, so lights and diffusers land on top of heads.
- Hanger spacing stretched past the allowed interval on long branch line runs.
- Branch line sizing tags missing or illegible, making it impossible to verify pipe size against the hydraulic calc later.
- Areas released for cover before the hydrostatic test pressure and duration are actually documented for that zone.
- Sprinkler heads sitting closer to ductwork, beams or light fixtures than the required clearance, only visible from above before the ceiling closes.
- Leaks found during test repaired but the area re-covered without a re-test being logged.
- Spare head cabinet missing the wrench or short on the required spare heads and types.
- Signage at valves and the riser missing or not matching the zone it actually controls.
Verified against
Families only, never clause numbers. Adoption varies by jurisdiction; confirm the edition your authority having jurisdiction enforces before you run a walk against it.
Categories and trades on the same jobs
Common questions
5 answers
- Which fire protection inspections do these checklists cover?
- Fire protection rough-in inspection checklist (rough-in): After branch lines and mains are hung and before ceiling grid or drywall closes in, and before the AHJ rough-in inspection is called. Fire protection pre-cover inspection checklist (pre-cover): After the branch lines and mains are complete and hydrostatically tested, before ceiling tile or hard lid closes the space above. Fire protection final inspection checklist (final): After escutcheons and covers are installed and the system is charged, before final acceptance testing and turnover. Fire protection preventive maintenance checklist (preventive maintenance): Monthly and quarterly rounds per the maintenance schedule, with an annual full system test.
- Who runs a fire protection inspection?
- The sprinkler foreman walking their own rough-in with the GC's superintendent. The sprinkler foreman with the GC's superintendent, releasing the area once the test is documented. The sprinkler foreman at trim-out, then the fire marshal or AHJ at final acceptance testing. The fire protection contractor or in-house fire life-safety tech on a scheduled inspection round.
- What most often sends fire protection work back?
- Head locations laid out to the sprinkler drawing but never checked against the actual reflected ceiling plan, so lights and diffusers land on top of heads. Hanger spacing stretched past the allowed interval on long branch line runs. Branch line sizing tags missing or illegible, making it impossible to verify pipe size against the hydraulic calc later. Areas released for cover before the hydrostatic test pressure and duration are actually documented for that zone.
- Which standards is fire protection work verified against?
- NFPA 13, published by the National Fire Protection Association; NFPA 25, published by the National Fire Protection Association. Adoption varies by jurisdiction. Confirm the edition your authority having jurisdiction enforces before you run a walk against it.
- Can I run these checklists in RTI?
- Yes. Start a free RTI workspace and load any of the 4 lists (54 items in total). The Photo Gate holds the submit button until every mandatory item is answered and its photos are attached, and approved inspections roll into a branded turnover package with a tamper evident audit trail.
Run these lists with the Photo Gate.