Expansion joint systems rough-in is the last time the work is fully visible. Once the cover inspection passes and the walls, ceilings and slabs close, every defect left behind becomes a demolition bill. This checklist walks the rough-in in the order the work goes in, with the photo each item needs before it gets buried. Work is commonly verified against manufacturer's published instructions, the applicable building code. Confirm the edition your authority having jurisdiction has adopted.
The checklist
Every item, and the photo evidence it needs
The photo count on each row is what RTI would require before the item can be submitted. Work the list here and watch the gate hold, or load it into RTI and let it enforce the real thing.
Joint schedule and delivery
Each joint run matched to its approved system
Every floor, wall, ceiling and roof joint on the drawings tied to the approved submittal for that run, with its movement rating and nominal width noted.
No photoFrame and cover packaging labels match the submittal
Model, size, finish and movement rating on the delivered frames and covers read against the approved submittal before any piece is cut or set.
Blockout and nosing
Blockout width and nosing correct for the rated movement
Gap measured against the system's movement range at the current temperature, nosing formed square and to the right depth for the cover.
Substrate and anchors sound at the joint edges
Edge concrete solid and clean, anchors set to the specified pattern and embedment, no crumbling or featheredged nosing.
Gap even end to end with no taper between the slab edges
Slab edges run parallel along the whole run; any taper or offset beyond what the frame can take up is flagged to the super before frames are set.
Both sides of the joint at the same elevation
Straightedge laid across the gap at intervals; any step between the two sides noted per run for the installer to shim or grind per the manufacturer.
Joint cavity clear of forms, debris and concrete bridges
Form boards, filler strips and concrete fins removed full depth, so nothing in the gap ties the two sides of the building together.
Frame setting
Frame rails set to the finished floor or wall height
Rails set to the finish elevation on the drawings, allowing for tile, carpet, topping or wall finish, so the cover lands flush once finishes are in.
Frames set at the gap the temperature chart gives today
Setting gap read from the manufacturer's temperature chart, measured at the frame and written on the joint log with the time and air temperature.
Anchor drilling checked against slab reinforcement
Anchor locations checked against the structural drawings, or the slab scanned first where it is post-tensioned; no cut tendons or bars at the joint edge.
No photo
Barrier continuity
Fire barrier continuous through the joint
Fire barrier packed continuous along the joint and carried through changes of plane, no gaps where the floor joint turns up a wall.
Water barrier continuous at the joint
Waterproofing or membrane lapped into the joint and continuous at transitions, drainage path maintained where the system sheds water.
Fire barrier matches the listed joint system on rated runs
On runs the drawings show as rated, barrier model, width range and orientation read against the listed system; unrated runs noted as such on the joint log.
No photo
Handoff to finishes
Finish crews told the frame height and the no-fill zone
Tile, flooring and wall finish foremen shown where each frame sits and told no mortar, grout, patch or fasteners go into the joint or across the frame.
No photoOpen joints covered where traffic crosses them
Plywood or the maker's temporary cover spans the open joint at traffic routes, fastened to one side only so it does not lock the gap.
What usually sends this back
The failures are almost always the evidence, not the work
- Blockout formed to a nominal width without accounting for the gap at the temperature the concrete was placed, so the system can't take its rated movement.
- The fire barrier at the joint stopped short at a change of plane, leaving an unsealed gap where the floor joint turns up the wall.
- Nosing anchors set into weak edge concrete that spalls the first time the cover is loaded, pulling the assembly loose.
Common questions
6 answers
- What does this expansion joint systems rough-in checklist cover?
- 15 items across 5 sections, covering joint schedule and delivery, blockout and nosing, frame setting, barrier continuity, and more. Each item spells out what the person walking the job is actually looking for, not just a box to tick.
- Who should run this inspection?
- The joint-system installer with the GC's superintendent, releasing the prepared joint before the cover assembly goes on.
- When in the schedule should this walk happen?
- After the blockout is formed and any nosing and anchors are set, before the cover assembly and adjacent finishes close over the joint.
- Why do these items ask for a photo?
- 11 of the 15 items call for photo evidence, 15 photos in all. A checklist answer without the photo is a claim; the photo is what makes the record worth something in a dispute and lets a reviewer approve work without re-walking the job.
- What most often fails an expansion joint systems rough-in inspection?
- Blockout formed to a nominal width without accounting for the gap at the temperature the concrete was placed, so the system can't take its rated movement. The fire barrier at the joint stopped short at a change of plane, leaving an unsealed gap where the floor joint turns up the wall. Nosing anchors set into weak edge concrete that spalls the first time the cover is loaded, pulling the assembly loose.
- Can I use this checklist in RTI?
- Yes. Start a free RTI workspace, build this list as a checklist, and the Photo Gate holds the submit button until every mandatory item is answered and its photos are attached. Approved inspections roll into a branded turnover package with a tamper evident audit trail.
Related checklists
Run it with the Photo Gate
A checklist nobody can submit half-finished
Load this list into RTI, stick a QR tag on the area it covers, and the submit button stays locked until every mandatory item is answered and the 15 required photos exist. Approved walks roll into a branded turnover package with a tamper evident record behind every line.
See all 508 checklists · 6741 items and 5984 photo requirements in total.