Nurse call system quarterly maintenance checklist
A quarterly nurse call system round is short on purpose: it catches the wear items that fail between annual services. This checklist is sized for a tech with a phone. Every item says what to look at and the photo that proves the round happened. Work is commonly verified against the applicable building code, manufacturer's published instructions. Confirm the edition your authority having jurisdiction has adopted.
The checklist
Every item, and the photo evidence it needs
The photo count on each row is what RTI would require before the item can be submitted. Work the list here and watch the gate hold, or load it into RTI and let it enforce the real thing.
Before testing
Charge nurse and nursing leadership told before test calls
Unit manager and charge nurse told which rooms will be tested and when, and patients in those rooms told test calls are coming and shown the backup call method.
No photoUnits tested one at a time so every patient keeps call
Only one unit or zone in test at a time, the rest in normal service, and patients in any room taken out of service told and shown the backup call method.
No photoFault and offline history reviewed since the last round
Supervision and fault history on the nurse call server or master reviewed, repeat offline stations and unanswered faults listed for the vendor to test first.
No photo
Call stations
Bedside, bath and pull-cord stations placed and functional
Each station present, cords reaching the floor where required, buttons and reset controls not damaged, station places a call when pressed.
Station cancel and reset work at the point of care
Call clears from the station itself, not only at the master, and the corridor light and annunciator drop when the call is reset.
Bed call cord or pillow speaker checked at each bed tested
Cord and plug undamaged and seated in the bedside jack, call button and any TV or light controls working, and unplugging it raises the cord-out alert where the jack is supervised.
Toilet and shower pull calls annunciate at bath priority
A pull at the toilet, and at the shower where there is one, shows as a bath call, not a routine call, with its own tone and light pattern, and cancels only in the room.
Staff emergency and code call tested at a room on each unit
Code team or operator warned first where the call pages them; the call shows above routine and bath calls with its own tone and light, then is cancelled in the room.
Annunciation
Corridor dome light and master station annunciate the call
A call lights the correct corridor dome, shows the correct originating station at the master, and the audible tone sounds, with the path observed end to end.
Zone lights at corridor turns lead staff to the room
Where fitted, zone lights at corridor turns and unit entries light for a call in their zone, in the same color or pattern as the room's dome light.
No photoCall shown at every staff, duty or master station the unit has
Test call shows the right room at each staff, duty or master station on the unit, and where stations have voice, staff and caller hear each other clearly.
Test call reaches the assigned wireless handset or badge
Where calls route to phones, pagers or badges, the call arrives on the assigned device with the right room, bed and priority, and answering it there shows at the master.
No photo
Backup
System backup power present and indicating healthy
Backup supply energized, no trouble or low-battery indication at the master, no stations showing offline.
No photo
Close-out
Tested units back in normal service and charge nurse told
Every test call cleared at the master, assignments and settings back to normal, backup call method withdrawn, and the charge nurse told testing is finished.
No photoRound results logged by room and bed
Stations tested, faults found and devices that missed calls logged by room and bed, with repairs raised to the vendor and the owner.
No photo
What usually sends this back
The failures are almost always the evidence, not the work
- A pull-cord or bath station calls but the corridor dome light and master station never annunciate, so nobody responds.
- A pull cord is missing or tucked out of reach, so the station it serves cannot be reached from the fixture it protects.
- The system runs on utility power with a dead backup, and the failure is invisible until a power blip drops the whole system.
Common questions
6 answers
- What does this nurse call system quarterly checklist cover?
- 15 items across 5 sections, covering before testing, call stations, annunciation, backup, and more. Each item spells out what the person walking the job is actually looking for, not just a box to tick.
- Who should run this inspection?
- The maintenance or low-voltage tech on the quarterly round; the field observes and documents, the licensed integrator tests and documents.
- When in the schedule should this walk happen?
- Every quarter, walked room by room. Calls that never annunciate are usually found only when someone actually presses the button.
- Why do these items ask for a photo?
- 7 of the 15 items call for photo evidence, 9 photos in all. A checklist answer without the photo is a claim; the photo is what makes the record worth something in a dispute and lets a reviewer approve work without re-walking the job.
- What most often fails a nurse call system quarterly inspection?
- A pull-cord or bath station calls but the corridor dome light and master station never annunciate, so nobody responds. A pull cord is missing or tucked out of reach, so the station it serves cannot be reached from the fixture it protects. The system runs on utility power with a dead backup, and the failure is invisible until a power blip drops the whole system.
- Can I use this checklist in RTI?
- Yes. Start a free RTI workspace, build this list as a checklist, and the Photo Gate holds the submit button until every mandatory item is answered and its photos are attached. Approved inspections roll into a branded turnover package with a tamper evident audit trail.
Run it with the Photo Gate
A checklist nobody can submit half-finished
Load this list into RTI, stick a QR tag on the area it covers, and the submit button stays locked until every mandatory item is answered and the 9 required photos exist. Approved walks roll into a branded turnover package with a tamper evident record behind every line.
See all 508 checklists · 6741 items and 5984 photo requirements in total.