Energy recovery ventilator (ERV) quarterly maintenance checklist

A quarterly energy recovery ventilator round is short on purpose: it catches the wear items that fail between annual services. This checklist is sized for a tech with a phone. Every item says what to look at and the photo that proves the round happened. Work is commonly verified against IMC, manufacturer's published instructions. Confirm the edition your authority having jurisdiction has adopted.

Items
5
Photos required
7

Who runs it

The HVAC or maintenance tech on the quarterly round, at the unit in the mechanical room or on the roof.

When in the schedule

Every quarter, since the ERV pulls outdoor air continuously and loads its filters faster than equipment that only runs on a call.

The checklist

Every item, and the photo that proves it

The photo count on each row is what RTI would require before the item can be submitted. Copy the list as is, or load it into RTI and let the gate enforce it.

01

Filters

  • Filters on both the supply and exhaust airstreams changed

    Both airstreams' filters pulled and checked, replaced when loaded, gaskets seated so air isn't bypassing the filter.

    2 photos
02

Recovery and drives

  • Recovery wheel turning or core clear

    Wheel rotating freely with its belt intact, or the fixed core faces clear, no debris packed into the media, seals contacting the wheel.

    2 photos
  • Supply and exhaust fans running clean

    Both fans running without bearing noise or vibration, belts on belt-drive units tensioned and not glazed.

    1 photo
03

Dampers and drains

  • Outdoor-air and exhaust dampers operate

    Dampers stroking fully open and closed with the unit, linkages tight, no blades stuck or bent, closing off when the unit is down.

    1 photo
  • Condensate drains flowing on both sides

    Drain pans and traps checked on the drain side, water flowing away, no standing water in the cabinet.

    1 photo

What usually sends this back

The failures are almost always the evidence, not the work

  • Only the supply-side filter changed while the exhaust-side filter, out of sight on the return, blinds off and chokes recovery.
  • Recovery wheel stalled or its belt slipping so the unit passes air but recovers nothing, and the energy penalty goes unnoticed.
  • Condensate drain on the exhaust side blocked, letting water back up into the cabinet or the recovery core.

Run it with the Photo Gate

A checklist nobody can submit half-finished

Load this list into RTI, stick a QR tag on the area it covers, and the submit button stays locked until every mandatory item is answered and the 7 required photos exist. Approved walks roll into a branded turnover package with a tamper-evident record behind every line.

Submission state

Mandatory items answered5 of 5
Photos attached4 of 7
Submit locked, 3 photos missing

The gate is enforced on the server, so it holds even if the phone is offline when the walk happens.

Verified against

Common questions

What does this energy recovery ventilator (erv) quarterly checklist cover?
5 items across 3 sections, covering filters, recovery and drives, dampers and drains. Each item spells out what the person walking the job is actually looking for, not just a box to tick.
Who should run this inspection?
The HVAC or maintenance tech on the quarterly round, at the unit in the mechanical room or on the roof.
When in the schedule should this walk happen?
Every quarter, since the ERV pulls outdoor air continuously and loads its filters faster than equipment that only runs on a call.
Why does every item ask for a photo?
7 of the 5 items call for photo evidence. A checklist answer without the photo is a claim; the photo is what makes the record worth something in a dispute and lets a reviewer approve work without re-walking the job.
What most often fails a energy recovery ventilator (erv) quarterly inspection?
Only the supply-side filter changed while the exhaust-side filter, out of sight on the return, blinds off and chokes recovery. Recovery wheel stalled or its belt slipping so the unit passes air but recovers nothing, and the energy penalty goes unnoticed. Condensate drain on the exhaust side blocked, letting water back up into the cabinet or the recovery core.