Water-source heat pump quarterly maintenance checklist
A quarterly water-source heat pump round is short on purpose: it catches the wear items that fail between annual services. This checklist is sized for a tech with a phone. Every item says what to look at and the photo that proves the round happened. Work is commonly verified against IMC, manufacturer's published instructions. Confirm the edition your authority having jurisdiction has adopted.
The checklist
Every item, and the photo evidence it needs
The photo count on each row is what RTI would require before the item can be submitted. Work the list here and watch the gate hold, or load it into RTI and let it enforce the real thing.
Access and lockout
Zone occupants told and the floor under the access panel covered
Occupants of the zone told the unit will be off for a short spell, desks and flooring under the ceiling access or closet door covered before the filter comes out.
No photoLock and tag on every circuit feeding the unit
Unit and any separate heat or control feed locked out, zero voltage proven. Running checks: panels on, people clear, locks off by whoever hung them, re-locked before hands go back in.
Air side
Filter replaced and coil face inspected
Filter changed and correctly sized, no bypass around the rack, coil face clean behind it with no matting or bent fins visible.
Condensate pan clear and float switch proven
Pan draining fully with no standing water or growth, trap primed, float switch lifted to confirm it interrupts the unit or alarms, secondary pan dry over occupied space.
Blower running clean and quiet
Wheel free of build-up, set screw tight, motor mounts sound, no rattle or bearing noise at each speed tap.
Return air path open at the closet louver or ceiling grille
Return grille, closet door louver or plenum opening to the unit free of stored boxes, blocked louvers or displaced ceiling tile, so the unit is not starved of return air.
Water side
Hose kit, isolation valves and connections dry
Supply and return hose kits, isolation ball valves and unions free of weeping or drips, no rust trail or wet insulation at the coax connections.
Water connections free of strain, kinks and chafe
Hoses or hard piping to the unit supported, not kinked, twisted or rubbing on the grid or cabinet edge, and not carrying the weight of the valves.
Loop flow and pressure drop reasonable across the unit
Supply and return pressures or the pressure drop across the coax read against the balanced value, no sign of a fouling strainer or a throttled autoflow starving the exchanger.
Operation and controls
Unit heats and cools on a call
Heat and cool each commanded from the thermostat, reversing valve shifting so discharge air changes over, entering and leaving water temperatures moving as expected, no fault on the board.
Lockout history read at the board light or building controls
Board light read through the cabinet sight hole, or the fault read at the thermostat or building controls, panels left on; any pressure or freeze lockout noted with its cause.
Close-out
Panels and tile back, locks removed and unit left running
Access panels and ceiling tile refitted, locks removed by whoever hung them, thermostat back on its normal schedule and the unit running on a call with no fault showing.
No photoWater readings and lockouts logged by unit tag and zone
Water temperature split set against the unit schedule and last quarter, plus pressure drop, filter condition and any lockout, entered by unit tag and zone.
No photo
What usually sends this back
The failures are almost always the evidence, not the work
- Filter skipped because the unit sits above a hard ceiling and the access panel is behind a light fixture, so airflow falls off and the coil starts to load.
- Condensate pan over an occupied space clogs and the ceiling tile stains before the float switch is ever proven to interrupt the unit.
- A hose kit or isolation valve weeping a slow drip onto the ceiling grid, mistaken for a roof leak until the water side is finally traced.
Verified against
Common questions
6 answers
- What does this water-source heat pump quarterly checklist cover?
- 13 items across 5 sections, covering access and lockout, air side, water side, operation and controls, and more. Each item spells out what the person walking the job is actually looking for, not just a box to tick.
- Who should run this inspection?
- The mechanical or maintenance tech on the quarterly round, reaching each unit through the ceiling access panel or the closet door.
- When in the schedule should this walk happen?
- Every quarter, walked unit by unit so a loaded filter or a weeping hose kit is caught before it shows up as a hot or cold zone complaint.
- Why do these items ask for a photo?
- 10 of the 13 items call for photo evidence, 13 photos in all. A checklist answer without the photo is a claim; the photo is what makes the record worth something in a dispute and lets a reviewer approve work without re-walking the job.
- What most often fails a water-source heat pump quarterly inspection?
- Filter skipped because the unit sits above a hard ceiling and the access panel is behind a light fixture, so airflow falls off and the coil starts to load. Condensate pan over an occupied space clogs and the ceiling tile stains before the float switch is ever proven to interrupt the unit. A hose kit or isolation valve weeping a slow drip onto the ceiling grid, mistaken for a roof leak until the water side is finally traced.
- Can I use this checklist in RTI?
- Yes. Start a free RTI workspace, build this list as a checklist, and the Photo Gate holds the submit button until every mandatory item is answered and its photos are attached. Approved inspections roll into a branded turnover package with a tamper evident audit trail.
Run it with the Photo Gate
A checklist nobody can submit half-finished
Load this list into RTI, stick a QR tag on the area it covers, and the submit button stays locked until every mandatory item is answered and the 13 required photos exist. Approved walks roll into a branded turnover package with a tamper evident record behind every line.
See all 508 checklists · 6741 items and 5984 photo requirements in total.